G9SX-AD[] / BC / EX

G9SX-AD[] / BC / EX

  • Facilitates partial or complete control system setup.
  • Solid-state outputs (excluding Expansion Units).
  • Detailed LED indications enable easy diagnosis.
  • TÜV SÜD certification for compliance with IEC/EN61508 (SIL3), EN ISO13849-1 (PLe/Safety Category 4).
  • Approved by UL and CSA.

Download Catalog Click Here!

Harga terbaik
Tersedia layanan instalasi

Tersedia layanan maintenance

Garansi 1 tahun

Gratis Konsultasi

G9SX-AD[] / BC / EX

  • Facilitates partial or complete control system setup.
  • Solid-state outputs (excluding Expansion Units).
  • Detailed LED indications enable easy diagnosis.
  • TÜV SÜD certification for compliance with IEC/EN61508 (SIL3), EN ISO13849-1 (PLe/Safety Category 4).
  • Approved by UL and CSA.

Download Catalog Click Here!

  • Facilitates partial or complete control system setup.
  • Solid-state outputs (excluding Expansion Units).
  • Detailed LED indications enable easy diagnosis.
  • TÜV SÜD certification for compliance with IEC/EN61508 (SIL3), EN ISO13849-1 (PLe/Safety Category 4).
  • Approved by UL and CSA.

Download Catalog Click Here!

Product Description

Introducing OMRON’s G9SX-AD[] / BC / EX series: versatile safety relay units facilitating control system setup with solid-state outputs and detailed LED indications. With TÜV SÜD certification for IEC/EN61508 (SIL3) and EN ISO13849-1 (PLe/Safety Category 4) compliance, and approval by UL and CSA, these units offer reliability and peace of mind in safety applications.

Ratings

Power input

 

ModelG9SX-AD322-[]/ADA222-[]G9SX-BC202-[]G9SX-EX-[]
Rated supply voltage24 VDC
Operating voltage range-15% to 10% of rated supply voltage
Rated power consumption *4 W max.3 W max.2 W max.

 

* Power consumption of loads not included.

Outputs

 

ModelG9SX-AD322-[]/ADA222-[]G9SX-BC202-[]
Instantaneous safety output *1
OFF-delayed safety output *1
P channel MOS-FET output
Load current:
0.8 A DC max./output *2 *3
P channel MOS-FET output
Load current:
0.8 A DC max./output *2 *3
Auxiliary outputPNP transistor output
Load current: 100 mA max./output

 

*1. While safety outputs are in the ON state, the following signal sequence is output continuously for diagnosis. When
using the safety outputs as input signals to control devices (i.e. Programmable Controllers), consider the OFF pulse
shown below.

G9SX-AD[] / BC / EX Specifications 5

*2. The following derating is required when Units are mounted side-by-side.
G9SX-AD322-[]/G9SX-ADA222-[]/G9SX-BC202-[]: 0.4 A max. load current/output
*3. A load current below 1 A DC/output can be used when the following outputs are used.
G9SX-AD322-[]/G9SX-ADA222-[]: 2 outputs or less
G9SX-BC202-[]: 1 output

Expansion Unit Ratings

 

ModelG9SX-EX-[]
Rated load250 VAC, 3 A/30 VDC, 3 A (resistive load)
Rated carry current3 A
Maximum switching voltage250 VAC, 125 VDC

 

Characteristics

 

ModelG9SX-AD322-[]/ADA222-[]G9SX-BC202-[]G9SX-EX-[]
Overvoltage category
(IEC/EN 60664-1)
IIII (Safety relay outputs
13 to 43 and 14 to 44: III)
Operating time
(OFF to ON state) *1
50 ms max. (Safety input: ON) *2
100 ms max. (Logical AND
connection input: ON) *3
50 ms max.
(Safety input: ON)
30 ms max. *4
Response time
(ON to OFF state) *1
15 ms max.10 ms max. *4
Accuracy of OFF-delay time *5Within ± 5% of the set valueWithin ± 5% of the set value
InputInput current10 mA min.
ON voltage11 V min.
OFF voltage5 V min.
OFF current1 mA max.
Maximum wiring length100 m max.
(External connection impedance: 100 Ω max. and 10 nF max.)
Reset input time100 ms min.
OutputON-state residual voltage3.0 V max. (safety output, auxiliary output)
OFF-state leakage current0.1 mA max. (safety output, auxiliary output)
Insulation
resistance
Between logical AND
connection terminals,
and power supply
input terminals and
other input and
output terminals
connected together
20 MΩ min. (at 100 VDC)
Between all terminals
connected together
and DIN track
20 MΩ min.
(at 100 VDC)
100 MΩ min.
(at 500 VDC)
Dielectric
strength
Between logical AND
connection terminals,
and power supply
input terminals and
other input and
output terminals
connected together
500 VAC for 1 min
Between all terminals
connected together
and DIN track
500 VAC for 1 min1,200 VAC for 1 min
Between different
poles of outputs
Between safety relay
outputs connected
together and other
terminals connected
together
2,200 VAC for 1 min
Vibration resistanceFrequency: 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude)
Shock
resistance
Destruction300 m/s2
Malfunction100 m/s2
DurabilityElectrical100,000 cycles min.
(rated load, switching
frequency: 1,800
cycles/hour)
Mechanical5,000,000 cycles min.
(switching frequency:
7,200 cycles/hour)
Ambient operating temperature-10 to 55°C (with no icing or condensation)
Ambient operating humidity25% to 85%
Terminal tightening torque *60.5 Nm
WeightApprox. 200 gApprox. 125 gApprox. 165 g

 

*1. When two or more Units are connected by logical AND, the operating time and response time are the sum total of the
operating times and response times, respectively, of all the Units connected by logical AND.
*2. Represents the operating time when the safety input turns ON with all other conditions set.
*3. Represents the operating time when the logical AND input turns ON with all other conditions set.
*4. This does not include the operating time or response time of Advanced Units that are connected.
*5. This does not include the operating time or response time of internal relays in the G9SX-EX-[].
*6. For the G9SX-[]-RT (with screw terminals) only.

Logical AND Connection

 

ModelG9SX-AD322-[]/ADA222-[]G9SX-BC202-[]G9SX-EX-[]
Number of Units connected per logical
AND output
4 Units max.
Total number of Units connected by
logical AND *1
20 Units max.
Number of Units connected in series by
logical AND
5 Units max.
Max. number of Expansion Units
connected *2
5 Units max.
Maximum cable length for logical AND
input
100 m max./output

 

Note: See Logical AND Connection Combinations Catalog for details.
*1. The number of G9SX-EX401-[] Expansion Units or G9SX-EX041-T-[] Expansion Units (OFF-delayed Model) not
included.
*2. G9SX-EX401-[] Expansion Units and G9SX-EX041-T-[] Expansion Units (OFF-delayed Model) can be mixed.

    Harga terbaik
    Tersedia layanan instalasi

    Tersedia layanan maintenance

    Garansi 1 tahun

    Gratis Konsultasi

    Jaminan Original

    Elmecon Multikencana distributor resmi berbagai brand ternama

    30 Hari Pengembalian

    Gratis pengembalian produk selama 30 hari setelah pemasangan

    Pengiriman Seluruh Indonesia

    Mencakup pengiriman keseluruh kota di Indonesia

    100% Aman

    Mulai dari pemesanan, pembayaran, pengiriman hingga instalasi.

    Ada Kebutuhan Besar untuk Proyek Anda?

    Konsultasi gratis bersama tim Engineer berpengalaman kami serta dapatkan penawaran terbaik hanya untuk Anda.