HDR-60-24

HDR-60-24

60 W/2.5 A DIN-rail 24 VDC power supply, universal 85 to 264 VAC or 120 to 370 VDC input voltage, -30 to 70°C operating temperature

Harga terbaik
Tersedia layanan instalasi

Tersedia layanan maintenance

Garansi 1 tahun

Gratis Konsultasi

HDR-60-24

60 W/2.5 A DIN-rail 24 VDC power supply, universal 85 to 264 VAC or 120 to 370 VDC input voltage, -30 to 70°C operating temperature

60 W/2.5 A DIN-rail 24 VDC power supply, universal 85 to 264 VAC or 120 to 370 VDC input voltage, -30 to 70°C operating temperature

Output Power Parameters
  • Wattage

    • 60 W
  • Voltage

    • 24 VDC
  • Current Rating

    • 0 to 2.5 A
  • Ripple and Noise

    • 150 mVp-p
  • Voltage Adjustment Range

    • 21.6 to 29 VDC
  • Setup/Rise Time at Full Load

    • 500 ms, 50 ms at 230 VAC
      500 ms, 50 ms at 115 VAC
  • Typical Hold Up Time at Full Load

    • 30 ms at 230 VAC
      12 ms at 115 VAC
Input Power Parameters
  • Voltage Range

    • 100 to 240 VAC (50 to 60 Hz)
      120 to 370 VDC
  • Typical Efficiency

    • 90%
  • Typical Current

    • 0.8 A @ 230 VAC, 1.2 A @ 115 VAC
  • Inrush Current (cold start)

    • 60 A @ 230 VAC, 30 A @ 115 VAC
Overload Protection
  • Rated Output Power

    • 105 to 160%
  • Protection Type

    • Constant current limiting, recovers automatically after fault condition is removed
Overvoltage Protection
  • Overvoltage Range

    • 30 to 36 V
  • Protection Type

    • Shut down operating voltage, repower on to recover
Physical Characteristics
  • Housing

    • Plastic
  • Dimensions

    • 52.5 x 90 x 54.5 mm (2.07 x 3.54 x 2.15 in)
  • Weight

    • 230 g (0.5 lb)
Environmental Limits
  • Operating Temperature

    • -30 to 70°C (-22 to 158°F)
  • Max. Operating Temperature at Full Load

    • 45°C (113°F)
  • Storage Temperature (package included)

    • -40 to 85°C (-40 to 185°F)
  • Ambient Relative Humidity

    • 20 to 90% (non-condensing)
Standards and Certifications
  • Safety

    • UL 508, EN 62368-1, UL 62368-1, IEC 62368-1
  • EMC

    • EN 55032/24, EN 61000-3-2 Class A, EN 61000-3-3
  • EMS

    • IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV
      IEC 61000-4-3 RS: 80 MHz to 6000 MHz: 10 V/m
      IEC 61000-4-4 EFT: Power: 2 kV
      IEC 61000-4-5 Surge: Power: 2 kV
      IEC 61000-4-6 CS: 10 V
      IEC 61000-4-8 PFMF
      IEC 61000-4-11
MTBF
  • Time

    • 927,560 hrs
  • Standards

    • MIL-HDBK-217F
Warranty
  • Warranty Period

    • 3 years

     

    Tags :

    Harga terbaik
    Tersedia layanan instalasi

    Tersedia layanan maintenance

    Garansi 1 tahun

    Gratis Konsultasi

    Related products
    Jaminan Original

    Elmecon Multikencana distributor resmi berbagai brand ternama

    30 Hari Pengembalian

    Gratis pengembalian produk selama 30 hari setelah pemasangan

    Pengiriman Seluruh Indonesia

    Mencakup pengiriman keseluruh kota di Indonesia

    100% Aman

    Mulai dari pemesanan, pembayaran, pengiriman hingga instalasi.

    Ada Kebutuhan Besar untuk Proyek Anda?

    Konsultasi gratis bersama tim Engineer berpengalaman kami serta dapatkan penawaran terbaik hanya untuk Anda.